TROUBLE SHOOTING CHART |
Sr.No |
Problem |
Cause |
Suggested Remedy |
1 |
Pumps does not starts. |
- Starting panel defective
- Overload protection out
- Starting panel defective
- Low line voltage
|
- Replace by new starter and check for continuity.
- Set relay properly.
- Replace with correct rating.
- Use adequate size cable.
- Wait till voltage recovers or contact electricity board.
|
2 |
Fuse blows when motor is running |
- Incorrect voltage or inadequate power supply.
- Overheated overload protection box.
- Defective control panel components
- Damaged motor cable or winding.
- Pump becomes sand locked
|
- Stabilise the voltage to rated and wait for adequate power supply.
- Overload relay to be replaced or adjusted to higher value.
- Replace starter if trips repetitively.
- Defective electrical components to be replaced.
- Check continuity in cable and wiring. Replace the cable. Rewind the motor if required.
- Remove dismantel and clean water passages inside the motor. Change the motor thrust pad if required.
|
3 |
Pumps operates but delivers little water. |
- Motor running lower than raled speed.
- Strainer / impeller / stage casing may be clogged.
- Defective rising main (leakage)
- System resistance of the pumpset is higher than estimated.
- Yield of the bore is not sufficient.
- Damaged pump parts.
|
- Check voltage / frequency. Replace cable with higher size if necessary.
- Dismantels the pump and clean strainer and water passage of impeller and stage casing if necessary replace them.
- Check the piping joints for leakage / choking.
- Replace pipes with higher size.
- Replace the pumpset with higher size.
- Lower the unit further if possible or throttle the sluice valve adjusting to flow rated.
- Replace correct components e.g. Impeller / Diffuser / Bushes / Sleeves / Neckring etc.
- Check slit / sand content of water to avoid premature wear.
|
4 |
Pump does not deliver any water. |
- Water level in borewell may have gone below level of pump.
- Total head of the system is higher than designed head of pumpset.
- NRV sand blocked / Wrongly connected NRV on delivery pipe.
- Motor does not start.
- Motor starts but doesn't pickup the rated speed.
|
- If possible lower the unit further
- Stop the unit until water level rises sufficiently.
- Operate the pumpset with throttle valve.
- Replace with suitable pumpset for higher head.
- Ensure that flow is not obstructed due to foreign bodies in valve or inferior quality of valve.
- Check the flow direction arrow on the NRV body connect correctly.
- Check for sand blockage clean and replace.
- Chek cable connection.
- Check for correctness of incoming power supply.
- Check for backup protection.
- Check voltage / frequency. Replace cable with higher size if necessary.
|
5 |
Fuse blow off or circuit breaker trips when motor is started |
- Defective control panel
- Defective wiring.
- Incorrect fuse component.
- Defective relay.
- Damaged motor winding or cable.
- Pump is sand locked.
- Pumpset might have blocked in crossed well.
- Pump and motor not coupled properly
|
- Repair / replace as per instruction.
- Replace and reset the starter only for checking the current drawn. Make sure that abnormal current is not drawn.
- Rewind motor / replace cable.
- Remove, dismantel and clean water passages inside the pump and ressemble.
- Move the unit and put straight and then strat otherwise shaft would have bend.
- Check and realign coupling and see freeness
|